Voltage Drop Calculator

Voltage Drop Calculator

Calculate voltage drop for your electrical wiring setup in Singapore

When it comes to safe and efficient electrical installations in Singapore, one of the most critical yet overlooked factors is voltage drop. Whether you’re wiring a residential HDB flat or planning a commercial upgrade, an excessive voltage drop can result in malfunctioning appliances, overheating, and even electrical hazards. At LS Electrician Singapore, we understand how important it is to calculate voltage drop accurately before finalizing your wiring plan. That’s why we’ve built a powerful and user-friendly Voltage Drop Calculator, designed specifically for Singapore’s unique electrical standards.

How to Use the Voltage Drop Calculator

Using our Voltage Drop Calculator on Electrician Singapore is incredibly simple, but understanding how each input affects the result is vital. When you open the tool, you’ll be prompted to enter basic electrical parameters like voltage, current (amps), cable length, cable size (in mm²), material type (Copper or Aluminium), and your phase type (Single Phase or Three Phase).

 

For example, a typical Singaporean household runs on 230V single-phase systems, while commercial buildings may use 400V three-phase systems. Entering the correct phase type ensures the calculator uses the right formula for resistance. The cable size and length determine how much resistance the current will face, while the material influences the resistivity. Once all values are entered, the calculator instantly provides the voltage drop in volts, percentage drop, and voltage at the load. We also include visual bar charts and color-coded feedback to help you interpret the results easily.

Understanding Voltage Drop

Voltage drop refers to the loss of electrical potential as current flows through a cable. It happens due to the resistance that the conductor offers to the flow of current. While some voltage drop is inevitable, it must remain within acceptable limits to ensure that appliances receive enough voltage to function properly.

 

In practical terms, if you’re running power to a garden shed 30 meters away from your main panel, the voltage at the shed might be significantly lower than the voltage at the source. This drop can cause lights to flicker or motors to underperform. In Singapore, most electricians follow the rule of thumb that voltage drop should not exceed 5% of the supply voltage. Anything beyond this could damage appliances and even pose fire hazards. At LS Electrician Singapore, we always measure voltage drop before committing to a wiring layout to ensure long-term safety and performance.

Voltage Drop Formula Explained

The calculation of voltage drop is based on Ohm’s Law and the physical properties of the cable. The simplified formula is:

Voltage Drop (V)=2×I×ρ×LA\text{Voltage Drop (V)} = \frac{2 × I × ρ × L}{A}Voltage Drop (V)=A2×I×ρ×L​

Where:

  • I is the current in amperes (A)

  • ρ is the resistivity of the conductor material (in ohm·mm²/m)

  • L is the one-way length of the cable (in meters)

  • A is the cross-sectional area of the conductor (in mm²)

The resistivity constant varies based on the material:

  • Copper = 0.0175 ohm·mm²/m

  • Aluminum = 0.0282 ohm·mm²/m

In three-phase systems, a correction factor of √3 is applied to the formula. This level of calculation can be complex, which is why our Voltage Drop Calculator handles everything for you automatically, ensuring accurate results tailored to your selected inputs. This allows electricians and homeowners to make quick, informed decisions about cable sizing and layout.

Voltage Drop Chart

Visualizing voltage drop data can help both professionals and DIYers choose the correct cable size and avoid excessive losses. Here is a simplified voltage drop chart based on standard 230V systems used in Singapore:

 

Cable Size (mm²)

Max Length for 10A

Max Length for 20A

Max Length for 32A

1.5

15 m

7.5 m

4.5 m

2.5

25 m

12 m

7.5 m

4.0

40 m

20 m

12 m

6.0

60 m

30 m

18 m

These are approximate values and assume copper cables in single-phase circuits. Use our Voltage Drop Calculator to get precise, real-time values for your specific project. The built-in bar graph and percentage meter will also highlight if your selected configuration falls within the safe range.

Single Phase vs Three Phase Voltage Drop

One of the most important considerations in calculating voltage drop is the phase type of your electrical system. In single-phase systems, voltage drop is calculated using the factor of 2×L. In three-phase systems, this is replaced with √3×L due to the different distribution of current across conductors.

 

In Singapore, HDB flats and most landed properties operate on a single-phase 230V supply, while industrial facilities and large commercial buildings often use a three-phase 400V supply. Choosing the correct phase type ensures that the calculator gives you accurate results.

 

At LS Electrician Singapore, we tailor all voltage drop calculations based on your installation’s supply type. For example, if you’re upgrading an EV charger system or installing a large pump, we’ll always check phase compatibility and voltage drop to prevent overloads and inefficiencies.

Voltage Drop in Singapore Wiring Systems

Singapore’s electrical system is regulated under the SS 638: Code of Practice for Electrical Installations, which aligns closely with international standards such as IEC and BS. Local installations commonly use PVC-insulated copper conductors, which offer excellent conductivity and resistance to heat.

 

The typical household voltage is 230V, with a frequency of 50Hz, and most wiring is designed for compact and efficient layouts. However, as homes become more electrified, with air conditioners, water heaters, and smart appliances, the risk of excessive voltage drop increases.

 

That’s why tools like the Voltage Drop Calculator from LS Electrician Singapore are becoming more essential. They help homeowners and professionals stay compliant while ensuring safety, energy efficiency, and long-term reliability.

Best Practices to Reduce Voltage Drop

To minimize voltage drop in your wiring system, consider the following best practices:

 

  • Use larger cables: A thicker cross-sectional area reduces resistance.

     

  • Keep cable runs short: Shorter distances mean less resistance and lower voltage loss.

     

  • Use copper over aluminum: Copper has lower resistivity and provides better performance for the same size.

     

  • Split high loads: Instead of using one long cable for multiple devices, use multiple circuits to distribute the load.

     

  • Avoid overloading circuits: Always account for future usage and allow a buffer for current draw.

     

 

At LS Electrician Singapore, we always design wiring layouts with these principles in mind, particularly for renovation and retrofit projects. With our calculator, you can identify where to upgrade the cable size or reduce the distance for optimal results.

FAQ

What is an acceptable voltage drop in Singapore?

For residential and commercial wiring, a voltage drop of less than 5% is generally acceptable. For sensitive equipment, aim for less than 3%.

Yes, the longer the cable, the greater the resistance, and therefore, the higher the voltage drop.

Use our calculator to input these values. Typically, a 6mm² copper cable is suitable, but verify based on your exact voltage and phase.

Copper has lower electrical resistivity, meaning it loses less voltage over the same distance and current.

Yes. Our tool allows you to choose between single and three-phase systems, making it suitable for all types of electrical installations in Singapore.